Power circuit characteristics | |
---|---|
Tripping class | 10A (standard IEC 60947-4-1 specifies a tripping time for 7.2 times the setting current Ir: class 10 A: between 2 and 10 seconds) |
Rated insulation voltage | 690V |
Rated impulse withstand voltage (Uimp) | 6kV |
Frequency limits of the operating current | 50...60Hz |
Setting range | 63...80A |
Fuses to be used with relay | aM - 80A gG - 125A |
Compatible with contactor | LC1E80 LC1E95 |
Power circuit connections | |
Flexible cable without cable end | 4...35mm2 |
Flexible cable with cable end | 4...35mm2 |
Solid cable without cable end | 4...35mm2 |
Tightening torque | 9N·m |
Auxiliary contact characteristics | |
Conventional thermal current | 5A |
Max sealed consumption of the operating coils of controlled contactors | 1.63A/220VAC |
Protection against short-circuits by gG or by GB2 | 5A |
Connection by screw clamp terminals | 2х1...2,5mm2 - flexible cable without cable end 2х1...2,5mm2 - flexible cable with cable end 2х1...2,5mm2 - solid cable without cable end |
Tightening torque | 1,7N·m |
Environment | |
Degree of protection | IP20 |
Protective treatment | "TH" |
Storage temperature | -60°C...+80°C |
Normal operation temperature without derating | -20°C...+60°C |
Operation temperature with derating | -20°C...+70°C |
Operating position | any |
Flame resistance | 850°C |
Shock resistance | 6gn - 11ms |
Vibration resistance | 3gn |
Dielectric strength at 50Hz | 6kV |
Operating characteristics | |
Temperature compensation | -20°C...+60°C |
Tripping threshold | 1,14±0,06 Ir A |
Sensitivity to phase failure | tripping current 130% of Ir on two phase, the last one at 0 |
Electrical diagram