Contactor LC1E2510F7

CE
Contactor LC1E2510F7
Request the price
Manufacturer: Schneider Electric
Model: 004.005.320
Weight: 360 g
In supplier's stock, Delivery time: 09/05/2018
The E-line contactors offer proven performance for resistive loads or large motor starting applications such as fans, crushers, pumps, compressors and overhead cranes. They offer high reliability with long mechanical and electrical life and the most complete line of accessories in the industry.
Main
rangeEasyPact
product nameEasyPact TVS
product or component typeContactor
device short nameLC1E
contactor applicationResistive load
Motor control
utilisation categoryAC-1
AC-3
poles description3P
pole contact composition3 NO
[Ue] rated operational voltage<= 690 V AC 50/60 Hz for power circuit
[Ie] rated operational current25 A (<= 60 °C) AC AC-3 for power circuit <= 440 V
36 A (<= 60 °C) AC AC-1 for power circuit <= 440 V
motor power kW15 kW at 660...690 V
11 kW at 380...400 V
11 kW at 415 V
11 kW at 440 V
5.5 kW at 220...230 V AC 50/60 Hz
15 kW at 500 V
control circuit typeAC 50/60 Hz
[Uc] control circuit voltage110 V AC 50/60 Hz
height74 mm
width45 mm
depth85 mm
product weight0.36 kg
colourGrey RAL 7011
Complementary
auxiliary contact composition1 NO
[Uimp] rated impulse withstand voltage6 kV (coil not connected to the power circuit) IEC 60947
[Ui] rated insulation voltage690 V conforming to IEC 60947-4-1
overvoltage categoryIII
Irms rated making capacity250 A - 440 V AC for power circuit conforming to IEC 60947-4-1
rated breaking capacity200 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current240 A at <= 40 °C - 10 s for power circuit
120 A at <= 40 °C - 60 s for power circuit
50 A at <= 40 °C - 600 s for power circuit
associated fuse rating10 A gG <= 690 V type 1 control circuit IEC 60947-5-1
40 A gG <= 690 V type 1 power circuit
average impedance2.5 mOhm at 50 Hz Ith 36 A for power circuit
power dissipation per pole3.2 W AC-1
1.6 W AC-3
control circuit voltage limits0.3...0.6 Uc at <= 55 °C drop-out 50/60 Hz
0.85...1.1 Uc at <= 55 °C operational 50/60 Hz
operating time12...22 ms on closing
4...19 ms on opening
mechanical durability10000000 cycles
operating rate1800 cyc/h at <= 60 °C
inrush power in VA95 VA at 20 °C (0.75) 60 Hz
95 VA at 20 °C (0.75) 50 Hz
hold-in power consumption in VA8.5 VA at 20 °C (0.3) 50 Hz
8.5 VA at 20 °C (0.3) 60 Hz
heat dissipation2...3 W for control circuit
minimum switching current5 mA control circuit
minimum switching voltage17 V control circuit
non-overlap time1.5 ms on energisation guaranteed between NC and NO contact
1.5 ms on de-energisation guaranteed between NC and NO contact
insulation resistance> 10 MOhm control circuit
electrical durability300000 cycles AC-3
350000 cycles AC-1
mounting supportPlate
DIN rail
connections - terminalsControl circuit : screw clamp terminals - 1 flexible cable(s) 1...4 mm² without cable end
Control circuit : screw clamp terminals - 2 flexible cable(s) 1...4 mm² without cable end
Control circuit : screw clamp terminals - 1 flexible cable(s) 1...4 mm² with cable end
Control circuit : screw clamp terminals - 2 flexible cable(s) 1...2.5 mm² with cable end
Control circuit : screw clamp terminals - 1 solid cable(s) 1...4 mm² without cable end
Control circuit : screw clamp terminals - 2 solid cable(s) 1...4 mm² without cable end
Power circuit : screw clamp terminals - 1 solid cable(s) 1.5...6 mm² without cable end
Power circuit : screw clamp terminals - 2 solid cable(s) 1.5...6 mm² without cable end
Power circuit : screw clamp terminals - 1 flexible cable(s) 1...6 mm² with cable end
Power circuit : screw clamp terminals - 2 flexible cable(s) 1...4 mm² with cable end
tightening torque1.5 N.m for control circuit
1.5 N.m for power circuit
Environment
standardsIEC 60947-5-1
IEC 60947-4-1
IEC 60947-1
product certificationsEAC
IP degree of protectionIP2x conforming to IEC 60529
protective treatmentTH IEC 60068 3
pollution degree3
ambient air temperature for operation-5...55 °C
ambient air temperature for storage-60...80 °C
permissible ambient air temperature around the device-20...70 °C at Uc
operating altitude3000 m without derating
fire resistance850 °C IEC 60695-2-1
mechanical robustnessVibrations contactor open 1.5 Gn, 5...300 Hz
Vibrations contactor closed 3 Gn, 5...300 Hz
Shocks contactor closed 10 Gn for 11 ms
Shocks contactor open 6 Gn for 11 ms
Dimensions and internal circuit
dimensions of LC1E2510F7 circuit of LC1-E2510F7
  • Contactor LC1E2510F5
    Contactor LC1E2510F5
    Price: $12.46
    1NO 25A 400V AC3 110V/50Hz
    Code: 004.005.052      In available: few

EasyPact TVS catalogue (english) [4,409 k]