Breaker Acti9 C60H-DC A9N61512 1P 20A C


RST
A9N61512 C60H-DC
Price: 31.08 ×
= 31.08
Model: 003.001.376
Weight: 113 g      Barcode: 3606480424137
In supplier's stock, Delivery time: 11/04/2019
The beakers A9N61512 supplementary protectors are used in direct current circuits (Industrial control and automations, transport, renewable energy...). They combine the following functions of circuit protection against short-circuit and overload currents, control and isolation.
Main

<table class="tddesk">
    <tbody>
        <tr>
            <th>range</th>
            <td>Acti 9</td>
        </tr>
        <tr>
            <th>product name</th>
            <td>Acti 9 C60H-DC</td>
        </tr>
        <tr>
            <th>product or component type</th>
            <td>Miniature circuit-breaker</td>
        </tr>
        <tr>
            <th>device short name</th>
            <td>C60H-DC</td>
        </tr>
        <tr>
            <th>device application</th>
            <td>Distribution</td>
        </tr>
        <tr>
            <th>poles description</th>
            <td>1P</td>
        </tr>
        <tr>
            <th>number of protected poles</th>
            <td>1</td>
        </tr>
        <tr>
            <th>[In] rated current</th>
            <td>20 A at 25 °C</td>
        </tr>
        <tr>
            <th>network type</th>
            <td>DC</td>
        </tr>
        <tr>
            <th>trip unit technology</th>
            <td>Thermal-magnetic</td>
        </tr>
        <tr>
            <th>curve code</th>
            <td>C</td>
        </tr>
        <tr>
            <th>breaking capacity</th>
            <td>Icu 10 kA at 220 V DC conforming to EN 60947-2<br>Icu 10 kA at 220 V DC conforming to IEC 60947-2<br>Icu 6 kA at 250 V DC conforming to EN 60947-2<br>Icu 6 kA at 250 V DC conforming to IEC 60947-2<br>Icu 20 kA at 110 V DC conforming to EN 60947-2<br>Icu 20 kA at 110 V DC conforming to IEC 60947-2</td>
        </tr>
        <tr>
            <th>utilisation category</th>
            <td>Category A conforming to EN 60947-2<br>Category A conforming to IEC 60947-2</td>
        </tr>
        <tr>
            <th>suitability for isolation</th>
            <td>Yes conforming to EN 60947-2<br>Yes conforming to IEC 60947-2</td>
        </tr>
    </tbody>
</table>
Complementary

<table class="tddesk">
    <tbody>
        <tr>
            <th>network frequency</th>
            <td>50/60 Hz</td>
        </tr>
        <tr>
            <th>[Ue] rated operational voltage</th>
            <td>250 V DC</td>
        </tr>
        <tr>
            <th>[Ics] rated service breaking capacity</th>
            <td>15 kA 75 % x Icu at 110 V DC conforming to EN 60947-2<br> 15 kA 75 % x Icu at 110 V DC conforming to IEC 60947-2<br> 4.5 kA 75 % x Icu at 250 V DC conforming to EN 60947-2<br> 4.5 kA 75 % x Icu at 250 V DC conforming to IEC 60947-2<br> 7.5 kA 75 % x Icu at 220 V DC conforming to EN 60947-2<br> 7.5 kA 75 % x Icu at 220 V DC conforming to IEC 60947-2</td>
        </tr>
        <tr>
            <th>[Ui] rated insulation voltage</th>
            <td>500 V DC conforming to IEC 60947-2<br> 500 V DC conforming to EN 60947-2</td>
        </tr>
        <tr>
            <th>[Uimp] rated impulse withstand voltage</th>
            <td>6 kV conforming to EN 60947-2<br> 6 kV conforming to IEC 60947-2</td>
        </tr>
        <tr>
            <th>contact position indicator</th>
            <td>Yes</td>
        </tr>
        <tr>
            <th>control type</th>
            <td>Toggle</td>
        </tr>
        <tr>
            <th>local signalling</th>
            <td>ON/OFF indication</td>
        </tr>
        <tr>
            <th>mounting mode</th>
            <td>Fixed</td>
        </tr>
        <tr>
            <th>mounting support</th>
            <td>35 mm symmetrical DIN rail</td>
        </tr>
        <tr>
            <th>comb busbar and distribution block compatibility</th>
            <td>Standard top or bottom</td>
        </tr>
        <tr>
            <th>9 mm pitches</th>
            <td>2</td>
        </tr>
        <tr>
            <th>product weight</th>
            <td>0.128 kg</td>
        </tr>
        <tr>
            <th>colour</th>
            <td>White</td>
        </tr>
        <tr>
            <th>mechanical durability</th>
            <td>20000 cycles</td>
        </tr>
        <tr>
            <th>electrical durability</th>
            <td>6000 cycles - 250 V DC<br> 3000 cycles - 250 V DC</td>
        </tr>
        <tr>
            <th>provision for padlocking</th>
            <td>Padlockable</td>
        </tr>
        <tr>
            <th>locking options description</th>
            <td>In position O</td>
        </tr>
        <tr>
            <th>tightening torque</th>
            <td>2.5 N.m top or bottom power circuit</td>
        </tr>
        <tr>
            <th>earth-leakage protection</th>
            <td>Without</td>
        </tr>
    </tbody>
</table>
Environment

<table class="tddesk">
    <tbody>
        <tr>
            <th>standards</th>
            <td>IEC 60947-2<br>EN 60947-2</td>
        </tr>
        <tr>
            <th>pollution degree</th>
            <td>3 conforming to EN 60947-2<br> 3 conforming to IEC 60947-2</td>
        </tr>
        <tr>
            <th>overvoltage category</th>
            <td>IV</td>
        </tr>
        <tr>
            <th>tropicalisation</th>
            <td>2 conforming to IEC 60068-2</td>
        </tr>
        <tr>
            <th>operating altitude</th>
            <td>2000 m</td>
        </tr>
        <tr>
            <th>ambient air temperature for operation</th>
            <td>-25...70 °C</td>
        </tr>
        <tr>
            <th>ambient air temperature for storage</th>
            <td>-40...85 °C</td>
        </tr>
    </tbody>
</table>
Размеры выключателей C60H-DC
36>182P1P815.573441681445